Where winters are mild, a heat pump can be the only heating system a house needs. It delivers two to four units of heat for each unit of electricity, against one for one from electric resistance heat. Size it for the cooling load, then add only as much backup strip heat as the coldest nights require.
How one machine does both jobs
A heat pump has the same parts as a split system air conditioner, plus three additions:
- A reversing valve that swaps the direction of refrigerant flow. The indoor coil becomes the hot coil and the outdoor coil becomes the cold one.
- A defrost control. In heating mode the outdoor coil runs colder than the air, and in damp weather near freezing it frosts over. The unit briefly switches back to cooling mode to melt the frost. Steam rising from the outdoor unit and a pause in warm air are normal during defrost.
- A second metering device so refrigerant can be metered in either direction.
Even cold air holds heat. A heat pump does not create warmth by burning or resisting anything. It moves it, which is why it can deliver more heat energy than the electrical energy it uses.
Balance point: where backup heat begins
- Heat pump output. It falls as the outdoor air gets colder.
- Heat the house loses. It rises as the outdoor air gets colder.
- The balance point, where the two are equal.
- Below the balance point, backup heat covers the gap.
- Where most winter nights fall in a mild climate: well to the warm side of the balance point.
For a typical house and a standard heat pump, the balance point lands somewhere around freezing. In central Florida, the outdoor temperature used for heating design is around 40°F, so a heat pump sized for the summer cooling load usually has heating capacity to spare on almost every winter night.
Sizing the heat pump and the strips
- Size for cooling. In a cooling-dominated climate the summer load sets the tonnage. Oversizing to gain heating capacity hurts summer humidity control for the sake of a handful of nights.
- Check heating output at your design temperature. The manufacturer's expanded performance table lists Btu/h at different outdoor temperatures. Compare the figure near your winter design temperature with the Manual J heating load.
- Size the strips for the gap, plus defrost. Backup heat should cover the shortfall on the coldest design night and temper the air during defrost. It does not need to heat the whole house alone unless you want it to serve as full emergency heat.
| Strip size | Heat output | Roughly equal to |
|---|---|---|
| 5 kW | 17,060 Btu/h | Heating from a 1.5 ton heat pump |
| 8 kW | 27,300 Btu/h | Heating from a 2 to 2.5 ton heat pump |
| 10 kW | 34,120 Btu/h | Heating from a 3 ton heat pump |
| 15 kW | 51,180 Btu/h | Heating from a 4 to 5 ton heat pump |
Strip kits are installed in the air handler and often need their own circuit. Larger strips mean heavier wire and a larger breaker, so a kit bigger than the house needs adds cost twice: once at installation and again every time it runs.
Reading the heating ratings
- HSPF2 is seasonal heating efficiency. The federal minimum for split heat pumps is 7.5. Higher numbers matter more the longer your heating season is.
- COP, the coefficient of performance, is efficiency at one outdoor temperature. A COP of 3 means three units of heat out for one unit of electricity in. Resistance strips have a COP of 1.
- Heating capacity at 47°F and 17°F are the two standard rating points. In a mild climate the 47°F figure describes most of your winter.
In a short heating season, do not pay much extra for a high HSPF2 or for cold-climate models built to hold capacity below 5°F. Put the money toward better cooling-season performance. The equipment overview explains SEER2 and EER2.
Running a heat pump well
- Avoid big thermostat setbacks in winter. A jump of several degrees can call the strips on to recover, wiping out the savings. Hold a steady temperature or use small setbacks.
- Know the "emergency heat" setting. It locks out the heat pump and runs the strips alone. Use it only when the outdoor unit has failed.
- Expect cooler supply air than a furnace gives. Heat pump air at the register feels lukewarm compared with gas heat. It runs longer and heats the house just as well.
- Keep the outdoor coil clear. In heating mode the outdoor unit needs free airflow just as it does in summer, and meltwater from defrost needs somewhere to drain.
- A burning-dust smell on the first cold night is usually the strips heating a year of settled dust. It should clear within minutes.
Heat pump checklist
- Tonnage chosen from the cooling load.
- Heating output at design temperature compared with the heating load.
- Strip heat sized for the gap and confirmed against the electrical panel's capacity.
- A thermostat made for heat pumps, with strip heat staged to come on only when needed.
- The outdoor unit raised enough for defrost water to drain, and anchored as described in the condenser unit guide.